Deploy test site / deploy (push) Successful in 47s
Twenty temperature tags on the pipes, each styled by its basis: green border for a Newbilt figure, amber for a design target or estimate, dashed for a value the vendor or a measurement still has to set. - Newbilt: steam main 10 bar ~180 C, header to the presses ~180 C, press outlets ~60 C (one per press, dimmed with the press when it is not installed in the selected case), supply header 20 to 25 C, oil cooler return <= 35 C (supply plus max. 10 K). - Design target or estimate: raw water ~28 to 30 C (ground temperature), feed to the boilers 90 to 95 C, heat pump feed loop <= 95 C, condensate after the traps <= 100 C (atmospheric return), extruder returns <= 35 C (2 to 3 kW at 4 l/min), heat pump source in <= 60 C, return header up to ~60 C mixed, chiller loop to HX-1 ~18 to 23 C (~2 K approach). - To be set: heat pump source out, warm tank mixed temperature, chiller loop return. The clicked details say where each figure comes from, including that Newbilt's 180 C is saturation at 10 bar absolute (~184 C at 10 bar gauge, to confirm). Legend explains the three tag styles. Checked headless (scripts/pw_sc_check.py, now also tag overflow and tag overlap with boxes, labels, symbols and each other): 20 tags, none overlapping or overflowing; no SVG or HTML overflow at 1600, 1258 and 390 px in all four cases; 32 boxes open their detail; no unstyled pipes; no errors.