grabowski c4d0e08c9f Add site massing model for the Mueang Chi candidate parcel
Models the plot and everything on it in FreeCAD, and writes up the
decisions the modelling forced.

Parcel geometry is traced from the DOL LandsMaps cadastral polygon and
reconciled against that portal's own measured edge lengths (40.86 + 26.61
/ 166.81 / 42.48 + 14.94 / 152.46 m), which the trace reproduces to within
about 1% with 1.67 m of closure error over a 444 m perimeter. Note the
mapped extent comes out near 9,570 sqm against a deed area of 8,266 sqm,
a ~16% gap that needs a surveyor before any offer.

On the site: 60x25 m production building on a 10 degree monopitch, a
45x38 m phase-2 building, roof and carport PV, fire and raw water tanks,
a detached boiler/chiller utility yard, perimeter wall and gate, guard
house, roofed staff parking, and the loading and fire-access roads.

Docs:
- scale.md: expansion headroom for a second building, and the detached
  utility yard, which frees ~126 sqm inside the main shed
- sustainability.md: roof orientation study (rotating the building for
  solar gains under 1 point and costs 4 m of clearance, so it stays
  aligned to the plot), and a new water supply section
- facility-security.md: fire water supply behind the existing
  suppression design

Figures marked as estimates are planning-grade, not engineering
calculations; the PV module spec is a generic placeholder, and zoning for
factory use on this plot is still unverified.
2026-07-29 23:00:09 +07:00

166 lines
8.8 KiB
Markdown
Raw Permalink Blame History

This file contains ambiguous Unicode characters
This file contains Unicode characters that might be confused with other characters. If you think that this is intentional, you can safely ignore this warning. Use the Escape button to reveal them.
# Facility: Security and Site Systems
What the plant needs beyond the production machinery. Access control, CCTV,
and whole-factory HVAC control are set requirements; the rest of this list
is what a plant of this profile definitely needs, to be refined during site
design.
## Climate control: whole-factory HVAC
The entire factory runs under continuous HVAC control, covering temperature,
humidity, and particulate matter (PM). This is a set requirement, not an
option per room.
- **Temperature and humidity**: the process spec already demands 20-26 °C at
35-60% relative humidity for pressing; the same conditioning extends to
the whole building so materials, masters, packaging stock, and electronics
never sit outside controlled conditions. PVC compound and paper packaging
are both humidity-sensitive.
- **Particulate matter**: filtration for the whole plant, with stricter
tiers by zone. Dust in a groove is an audible defect, so the cutting room
and galvanics clean room run at the tightest spec with positive pressure;
pressing and packaging run cleaner than ambient; offices and logistics at
a baseline tier. Northern Thailand's burning season (roughly February to
April) brings some of the world's worst PM2.5 episodes, so intake
filtration and building tightness must be designed for those peaks, not
for average days.
- **Continuous monitoring and alarms**: temperature, humidity, and PM
sensors logging in every zone, with alarms on excursions, tied into the
plant monitoring below.
- **Energy design**: conditioning a whole factory in a tropical climate is
a major electrical load on top of the 250 kW process cooling, and it must
be included in the solar PV and battery sizing from the start. Heat
recovery from the press hall (steam, hydraulics, and hot PVC all reject
heat) and from compressors should feed the design rather than fight it.
## Physical security
- **Access control**: zoned, not just at the gate. Minimum zones: general
production, galvanics clean room (controlled access is already a safety
requirement), chemical storage, master/stamper archive, server/IT room,
finished goods and shipping. Badge or biometric, with logs.
- **CCTV**: entrances, perimeter, loading dock, production floor, chemical
storage, archive. Retention policy to be defined; Thai PDPA (personal data
protection) applies to camera footage of staff and visitors.
- **Intrusion alarm** with monitoring, covering off-hours.
- **Perimeter and lighting**: fencing appropriate to the site, lit
approaches and parking.
- **Visitor management**: sign-in, escort rules, PPE issue at entry, no
unaccompanied access to production or galvanics.
## Protecting the irreplaceable
- **Master and stamper archive**: fathers and mothers are unique metal
parts; a destroyed father can mean re-cutting and re-plating a release.
The archive room needs fire-rated construction or safes, climate control,
access logging, and an off-site strategy for the most critical masters.
- **Client audio**: pre-release music is a high-value leak target, and
labels ask about it before they send masters. Isolated storage for client
files, encrypted transfer and at-rest storage, strict need-to-know access,
and a written policy the sales team can show clients.
- **Chemical inventory**: silver nitrate is valuable and regulated; nickel
salts are hazardous. Locked storage, inventory tracking, and controlled
issue to the galvanics team.
## Fire and life safety
- **Fire detection and alarm** throughout; suppression matched to each zone
(hot PVC and hydraulic oil in pressing, chemistry in galvanics, paper and
cartons in packaging/finished goods, and the boiler room).
- **Boiler room safety**: the steam generator (10 bar, 180 °C) needs its own
room, safety valves, fuel shutoff interlocks, and inspection per Thai
boiler regulations (Department of Industrial Works requirements, licensed
boiler operator).
- **Emergency equipment in galvanics**: eyewash stations and emergency
shower at the plating line, spill kits, and neutralizing agents.
- **Emergency lighting, marked exits, assembly point**, and first-aid
coverage on every shift.
### Suppression design position: zoned, not full-building gas
A full-building gas suppression system is ruled out: gas agents only work in
sealed volumes that can hold concentration, which a ventilated production
hall with people and loading doors cannot, and CO2 flooding is lethal in
occupied spaces. The design position is zoned suppression:
- **Clean agent gas** (FK-5-1-12, sold as Novec 1230, or inert gas such as
IG-541) only in small, sealed, high-value rooms: the server/IT room,
electrical switchrooms, PLC/control cabinets (in-cabinet micro systems),
and above all the master/stamper archive, where sprinkler water would
destroy lacquers and paper records and corrode the metal parts even in a
minor event.
- **Water** (sprinklers, or water mist where equipment matters) for the
large spaces: production, warehouse, and packaging/finished goods, where
paper cartons are the largest fire load in the building. The press hall's
specific risk is a hydraulic oil spray fire (200 L at 180 bar); water
mist handles oil fires well and is gentler on machines than deluge.
- **Battery stack (BESS)**: gas does not stop lithium thermal runaway. Per
NFPA 855 practice the stack needs off-gas and early-smoke detection,
electrical isolation on alarm, physical separation from production
(ideally its own enclosure), and deflagration venting. Detection and
containment over suppression.
- **Galvanics**: low fire load (aqueous baths); local clean-agent
protection for rectifier cabinets is sufficient.
### Fire water supply
Sprinklers, water mist, and hose reels are only as good as the water behind
them. Mains pressure and flow in Mueang Chi cannot be assumed adequate for a
sprinkler demand, so the site carries its own reserve and pumps.
- **Stored reserve: ~200 m³**, in a dedicated fire water tank (planning
figure: 9 m diameter × 4 m, roughly 204 m³ usable above the pump suction).
Basis is an Ordinary Hazard Group 2 sprinkler demand of about 1,100 L/min
over the design area, plus a 950 L/min hose-stream allowance, held for 90
minutes. **This is a planning estimate, not a fire-engineering
calculation** — the real number comes out of the hydraulic design.
- **Dedicated, not shared**: the reserve is not drawn on by process or
sanitary water, and the tank refills automatically.
- **Fire pump set**: duty pump, standby pump, and a jockey pump holding
ring-main pressure, in a pump house beside the tank. The duty pump needs a
power path that survives a plant trip (diesel drive, or a supply ahead of
the main breaker) — the BESS is not a substitute.
- **Ring main and hydrants** around the building, laid out so an appliance
can reach any elevation, with the yard kept clear for access.
- **Siting**: the tank stands in the front yard between the road and the
building, reachable directly from the frontage without entering the
production yard. At 4 m tall it sits well below the building's 7 m low
eave, so it never shades the roof PV.
**Warehouse racking height drives the real number.** If finished-goods
storage goes above roughly 3.7 m, the commodity classification and sprinkler
design change, and the stored volume grows with them. Fix the racking height
before the fire design is frozen, not after.
The property insurer will drive much of the final specification, so involve
them before the design is fixed. The archive gas system and the BESS
detection affect room layout and belong in the site design brief early.
## Plant systems and monitoring
- **Utility monitoring and interlocks**: fume-extraction interlocks on the
galvanics line (no extraction, no plating), steam and compressed-air
pressure monitoring, leak detection, and safe-shutdown sequences.
- **UPS and controlled shutdown** for the IT room, access control, alarms,
and the press PLCs (a power cut mid-cycle should never leave a press in an
unsafe state; the battery stack can carry critical loads).
- **Lightning protection and grounding**: northern Thailand has intense
storm seasons; the PV array, steel structures, and electronics all need a
proper LPS and earthing design.
- **Environmental monitoring**: the whole-factory HVAC monitoring above
(temperature, humidity, PM in every zone), with the archive and clean room
as the most tightly alarmed spaces.
## Compliance anchors (Thailand)
- Factory license (Ror.Ngor. 4) and Department of Industrial Works
requirements for the machinery classes and chemical quantities involved
- Boiler registration and licensed operator requirements
- Hazardous substance registration for the plating chemistry
- PDPA compliance for CCTV and personnel data
- Local fire codes and building permits during construction
All of this belongs in the site design brief, so contractors quote it from
day one rather than retrofitting it.