Add solar hardware plan: Deye hybrid inverters + Gobel Power 271 kWh BESS
Includes open engineering checks: battery rack voltage vs Deye model window, Gobel safety certifications, and peak-shaving-scale framing
This commit is contained in:
1 parent
4c44b39e0c
commit
6281c5b223
2 files changed
+26
-1
No files matched your search
@@ -177,6 +177,17 @@ at 10 bar / 180 °C) and the 250 kW cooling system.
|
|||||||
- A large rooftop/ground PV installation is planned. Northern Thailand's solar
|
- A large rooftop/ground PV installation is planned. Northern Thailand's solar
|
||||||
irradiance is favorable, and daytime-heavy production shifts align well with
|
irradiance is favorable, and daytime-heavy production shifts align well with
|
||||||
PV output.
|
PV output.
|
||||||
|
- The chosen hardware direction: multiple large **Deye** three-phase hybrid
|
||||||
|
inverters (30 to 80 kW class, parallelable up to 10 units) paired with a
|
||||||
|
**Gobel Power** high-voltage LiFePO4 battery stack at **271 kWh** (15
|
||||||
|
stacked 18 kWh packs, LFP 314 Ah cells, rated 8000+ cycles). Deye is an
|
||||||
|
officially supported protocol on the Gobel BMS, and Deye has established
|
||||||
|
Thai distribution. Two engineering checks are open: matching the battery
|
||||||
|
rack's DC voltage window to the specific Deye model (a full 15-pack rack
|
||||||
|
can exceed the 800 V window of the smaller Deye series), and obtaining
|
||||||
|
Gobel's safety certifications (not published) for a Thai commercial
|
||||||
|
install. At 271 kWh the stack is a peak-shaving and ride-through buffer,
|
||||||
|
not full off-grid autonomy, against loads like the 250 kW cooling system.
|
||||||
- The machine load and cooling system are straightforward PV targets.
|
- The machine load and cooling system are straightforward PV targets.
|
||||||
- Steam is the open engineering question. Options under evaluation include an
|
- Steam is the open engineering question. Options under evaluation include an
|
||||||
electric boiler (maximizes the solar share), a biomass boiler (locally
|
electric boiler (maximizes the solar share), a biomass boiler (locally
|
||||||
|
|||||||
@@ -139,7 +139,21 @@ Open: identify and qualify Thai/regional PVC compound producers.
|
|||||||
|
|
||||||
## 8. Utilities and Site (customer-supplied around the machines)
|
## 8. Utilities and Site (customer-supplied around the machines)
|
||||||
|
|
||||||
- Solar PV installation (large; sizing open until site selection)
|
- Solar PV installation (large; panel and array sizing open until site
|
||||||
|
selection)
|
||||||
|
- Solar inverters: multiple Deye three-phase HV hybrid units. Verified
|
||||||
|
series SUN-29.9/30/35/40/50K-SG01HP3 (battery window 160-800 V, up to 10
|
||||||
|
in parallel, IEC 61727/62116/62109 certified); larger SUN-60/70/75/80K
|
||||||
|
SG02HP3 series to be confirmed via datasheet. Thai distribution exists
|
||||||
|
(Solar Nicolo, solaris.co.th)
|
||||||
|
- Battery storage: Gobel Power (Shenzhen, est. 2012) GP-SRA-HV314 HV rack
|
||||||
|
BESS, 271 kWh = 15 stacked 18 kWh packs (LFP 314 Ah, 1P18S), DC 225-985 V,
|
||||||
|
8000+ cycles, ~135 kW continuous discharge at 0.5P, CAN/RS485 with "Deye
|
||||||
|
CAN HV" protocol support. Listed USD 39,900-58,000, 50-60 day lead from
|
||||||
|
China. Open checks: rack voltage vs. chosen Deye model's battery window
|
||||||
|
(full 15-pack rack can exceed 800 V), safety certifications
|
||||||
|
(UN38.3, IEC 62619, CE) not published, no performance warranty published,
|
||||||
|
no Thai distributor
|
||||||
- Steam generation (electric, biomass, or solar-thermal assist under
|
- Steam generation (electric, biomass, or solar-thermal assist under
|
||||||
evaluation; Deepgrooves NL runs presses on wood-fired biomass boilers as a
|
evaluation; Deepgrooves NL runs presses on wood-fired biomass boilers as a
|
||||||
precedent)
|
precedent)
|
||||||
|
|||||||