Archive room: mobile shelving for the father and mother archive
Deploy test site / deploy (push) Successful in 43s
Deploy test site / deploy (push) Successful in 43s
Planned (October 2026, user): the archive in the office gets mobile archive shelving, A-Z Solutions (Vienna) as the reference (a-z-solutions.eu, checked October 2026: hand wheel or electric drive, lockable, rails need early floor planning; no published prices). facility-security.md, new section under Protecting the irreplaceable: what it holds (fathers and mothers, ~1,200 to 2,400 parts a year; a reference pressing per title only as a proposal), sizing estimates (about 0.2 kg per part, ~3 mm and ~75 kg per shelf metre; in the Payap office's ~4 x 5.75 m room two fixed runs, four double carriages and one aisle hold ~150 shelf metres, ~50,000 parts, 20+ years), what it asks of the building (ground slab at full rating, ~11 kN/m2 under the block; rails in the screed fixed before the floor finish; geared hand wheel; gas, climate, leak sensor, access control; barcoded box addresses), open points (quotes from A-Z and a Thai supplier, storage format from the galvanics vendors, fathers in a second compartment or off site). Mirrors: site-candidates.md (office ground floor), phase 1 RFQ (archive keeps the full slab rating if the slab is zoned), digital-factory.md (archive location as box and shelf position, sets per mother), equipment-suppliers.md (section 8 entry), total-investment.md added scope (to quote, not in the sum).
This commit is contained in:
1 parent
475623e9f2
commit
4f02d9a7a9
6 files changed
+93
-3
No files matched your search
@@ -68,6 +68,80 @@ option per room.
|
||||
salts are hazardous. Locked storage, inventory tracking, and controlled
|
||||
issue to the galvanics team.
|
||||
|
||||
### Archive room: mobile shelving
|
||||
|
||||
Planned (October 2026): the archive in the office is fitted with **mobile
|
||||
archive shelving**, carriages on floor rails that close up into one block
|
||||
and open a single aisle where it is needed. The reference is A-Z
|
||||
Solutions' archive shelving (Vienna; fahrbare Archivregale,
|
||||
https://www.a-z-solutions.eu/buero-archiv/archivregale, checked October
|
||||
2026): hand wheel or electric push-button drive, optional front panels,
|
||||
lockable, and the vendor asks to be involved early because the rails set
|
||||
requirements on the floor and the room layout. Prices are not published.
|
||||
|
||||
**What it holds.** The father and the mother of every side (decided
|
||||
October 2026, [galvanics](equipment/galvanics.md)): 4 parts per title,
|
||||
about 1,200 to 2,400 a year at full capacity, in protective sleeves,
|
||||
standing in labelled boxes. Also paper records that have to be kept as
|
||||
originals. A reference pressing of every title could go here too; that is
|
||||
a proposal, not decided.
|
||||
|
||||
**Size, estimates.** A 12" father or mother grows on a 14" lacquer: about
|
||||
35 cm across, 0.25 mm thick, ~9.6 dm² ([plant
|
||||
operation](plant-operation.html) and galvanics figures), so about 0.2 kg of
|
||||
nickel. In a sleeve with a separator, assume ~3 mm of shelf per part:
|
||||
~330 parts and ~75 kg per shelf metre, on 400 mm deep shelves with ~400 mm
|
||||
clear height, five levels to ~2.2 m. In the Payap scenario's office the
|
||||
archive is a ground-floor room of about 4 × 5.75 m
|
||||
([site candidates](site-candidates.md)). With the rails along the long
|
||||
side it takes two fixed single-sided runs, four double-sided carriages
|
||||
about 3 m long and one ~0.9 m working aisle: ~150 shelf metres, roughly
|
||||
50,000 parts, which is 20 years or more of fathers and mothers at full
|
||||
capacity. Static shelving with an aisle between every pair of runs
|
||||
would hold about 60 % of that.
|
||||
|
||||
**What it asks of the building.**
|
||||
|
||||
- **Floor load.** Fully loaded, a double carriage carries about a tonne
|
||||
per metre of length: ~11 kN/m² under the shelving block and ~6 kN/m²
|
||||
averaged over the room (estimates), above an office floor. The archive stays on the ground slab, and
|
||||
that slab keeps the full rating if the slab is zoned lighter under
|
||||
offices ([phase 1 RFQ](finance/phase1-construction-rfq.md)).
|
||||
- **Rails.** Set into the floor screed during fit-out, or on a raised
|
||||
floor ramped at the door, so the shelving layout and the rail positions
|
||||
are fixed before the floor finish. Rail type, depth and floor flatness
|
||||
tolerance come from the shelving supplier.
|
||||
- **Drive.** A geared hand wheel with an aisle lock is enough for a room
|
||||
one or two people use and has nothing to fail; electric drive is an
|
||||
option, not a need.
|
||||
- **The room around it** stays as above: clean-agent gas suppression
|
||||
(the suppression designer confirms the agent reaches into the closed
|
||||
carriage block), climate control with the archive in the tightest
|
||||
monitoring tier ([digital factory](digital-factory.md)), a water-leak
|
||||
sensor along the rails, lockable carriages behind the room's access
|
||||
control.
|
||||
- **Locations.** Every box carries a barcode and every position an
|
||||
address (carriage, face, level, slot); the factory application records
|
||||
each part's archive location there, so a repress order says which box
|
||||
to pull.
|
||||
|
||||
**Open points.**
|
||||
|
||||
- **Quotes:** A-Z Solutions and a Thai or regional mobile-shelving
|
||||
supplier against the same spec (carriages ~3 m, five levels, 400 mm
|
||||
shelves, at least ~100 kg per shelf level per metre, geared hand wheel
|
||||
with aisle lock, central lock, rail embedding detail, delivery and
|
||||
installation in Chiang Mai). Steel shelving shipped from Austria is
|
||||
heavy, so the A-Z system is the reference spec rather than the default
|
||||
buy.
|
||||
- **Storage format:** sleeves, boxes, passivation and humidity for
|
||||
archived nickel parts, from the galvanics vendors
|
||||
([open questions](equipment/galvanics.md#open-questions-for-the-quotes)).
|
||||
- **Two compartments:** with fathers and mothers in one room, one event
|
||||
can take both. Keeping the fathers (rarely pulled) in a second fire
|
||||
compartment or off site, and the mothers (pulled for every repress) in
|
||||
this room, would meet the off-site point above.
|
||||
|
||||
## Fire and life safety
|
||||
|
||||
- **Fire detection and alarm** throughout; suppression matched to each zone
|
||||
|
||||